PERBANDINGAN SUSUT DAYA DAN SUSUT ENERGI MENGGUNAKAN PERHITUNGAN MANUAL DAN SIMULASI ETAP PADA JARINGAN DISTRIBUSI PENYULANG MATARAM GI NEW JAKABARING
During the process of distributing electrical energy, there are power losses and energy losses that result in unreliable power quality. The purpose of this research is to find out how much power and energy losses occur in the Mataram feeder in March 2024, and compare the percentage value of power losses with SPLN standards. This research uses two methods, namely manual calculation and simulation using ETAP 19.0.1 software. The results of the power losses value obtained by manual calculation are 2.3849 kW at noon peak load and 5.2397 kW at night peak load. Meanwhile, the calculation with ETAP simulation obtained a power loss value of 2.232 kW at noon peak load and 5.078 kW at night peak load. The value of energy losses on the Mataram feeder was obtained at 3.8182 kW with an average daily energy loss value of 91.6361 kWh. Based on the SPLN 1:1978 standard, the percentage of power losses allowed is 2%. The calculation results show that the percentage of power losses on the Mataram feeder is still within safe limits, with a power loss value of 0.13% at the afternoon peak load and 0.21% at the evening peak load.