Skripsi
ANALISA JATUH TEGANGAN JARINGAN DISTRUBSI PRIMER 20KV PADA PEYULANG JAMBI DI GARDU INDUK TALANG RATU PALEMBANG
Electricity will become increasingly important in people's lives over time. This is because almost all human activities rely on electrical energy, especially in the current modern era where technology is involved in every aspect of life. Therefore, PT PLN (Persero) strives to meet Indonesia's electricity needs through various means, one of which is through electricity distribution. In the distribution sistem, there are factors that can reduce the optimality of an electrical power sistem. This reduction is known as voltage drop in the distribution channels. Although unavoidable, it can be minimized. Therefore, research is conducted to analyze the voltage drop that occurs in the Jambi Substation of Talang Ratu Palembang by calculating the type and length of conductors, channel currents, loads and capacities of distribution transformers, as well as voltage drop calculations. Based on the calculations, the voltage drop value obtained is 56,6217 volts with a percentage of 0.2839%. The observed voltage drop value is still within the standardization set by PT PLN (Persero) in SPLN 1:1995, which is +5% and -10% of its operating voltage.
Inventory Code | Barcode | Call Number | Location | Status |
---|---|---|---|---|
2307005515 | T122999 | T1229992023 | Central Library (Referens) | Available but not for loan - Not for Loan |
No other version available