OPTIMALISASI RANCANGAN SISTEM PENTANAHAN PEMBANGUNAN STASIUN PENYIMPANAN AVTUR PULAU LAYANG BERBASIS SOFTWARE ETAP 12.6.0
In the power distribution system, ground faults and lightning strikes are the most common causes of disturbances. This interference will cause the hazard to rise or fall, endanger people's lives and damage electronic equipment. It takes the design of a grounding system design that meets the standards and obtains the values of the voltage and affection calculations on the Construction of the PT. Pertamina (Persero). Then design a grounding system using ETAP 12.6.0 software with the Finite Element Method (FEM) method to simulate the grounding system with the standard calculation system used, namely the IEEE Std standard. 80-2000 entitled IEEE Guide for Safety in AC Substations Grounding to get the value of connection and secure connection. With some adjustments based on the initial design, the Grid-Rod grounding system that meets the safety standards is 1 x 1 meter between grids with the number of conductors on the long and wide sides are nx = 4 and ny = 7, with conductor planting as far as 5 meters from the ground surface. and the number of grounding rods with a length of 3 meters used as many as 24 rods. This design produces a grounding limit value of 0.071 Ohm, a touch voltage of 699.9 Volts and a step voltage of 114.3 Volts which meet the IEEE Std safe standards. 80-2000 because Amin < Aproyek dan dmin < dproyek, Em < E touch 70, dan Es < Estep70.