ANALISA PENGARUH KETIDAKSEIMBANGAN BEBAN TERHADAP EFISIENSI TRANSFORMATOR DISTRIBUSI DI KOMPLEK PERUMAHAN PUSRI SAKO PALEMBANG.

Wulandari, Septiarani - Personal Name;

Penilaian

0,0

dari 5
Penilaian anda saat ini :  

In this time, electricity is a requisite that must be met. To produce a good distribution and service, in planning the electrical system must attended to the balance of loads per phase. An unbalanced load will leads current in the neutral wire, losses in the transformer and affect the value of the efficiency of a transformer. Based on the results of research conducted on distribution transformers in the Pusri Sako Housing Complex, it was found that the load imbalance value caused a neutral current in the distribution transformer PB 97. The value of neutral current before equalization burden on the direction C and majors D is of 62.10 A and 21.10 A after load distribution are 0.78 A and 0.3 A. And the value of copper losses (before load distribution is 4.705 KW and after load distribution is 4.384 KW. The value of losses in the neutral current before load distribution is 0.533 KW and after load distribution is 0.0000036 KW. Efficiency value increased after equalization, although not so much. The percentage of transformer efficiency before load equalization is 86.68% and the percentage of transformer efficiency after load distribution is 90.05 %.


Availability
Inventory Code Barcode Call Number Location Status
2107003030T555292T555292021Central Library (Referens)Available but not for loan - Not for Loan
Detail Information
Series Title
-
Call Number
T555292021
Publisher
Inderalaya : Jurusan Teknik Elektro, Fakultas Teknik Universitas Sriwijaya., 2021
Collation
xiv, 46 hlm,: ilus.; 29 cm
Language
Indonesia
ISBN/ISSN
-
Classification
621.314 07
Content Type
Text
Media Type
-
Carrier Type
-
Edition
-
Subject(s)
Jurusan Teknik Elektro
Transformator
Specific Detail Info
-
Statement of Responsibility
MURZ
Other version/related

No other version available

File Attachment
  • ANALISA PENGARUH KETIDAKSEIMBANGAN BEBAN TERHADAP EFISIENSI TRANSFORMATOR DISTRIBUSI DI KOMPLEK PERUMAHAN PUSRI SAKO PALEMBANG.
Comments

You must be logged in to post a comment

The Sriwijaya University Library
  • Information
  • Services
  • Librarian
  • Member Area

About Us

As a complete Library Management System, SLiMS (Senayan Library Management System) has many features that will help libraries and librarians to do their job easily and quickly. Follow this link to show some features provided by SLiMS.

Search

start it by typing one or more keywords for title, author or subject

Keep SLiMS Alive Want to Contribute?

© 2025 — Senayan Developer Community

Powered by SLiMS
Select the topic you are interested in
  • Computer Science, Information & General Works
  • Philosophy & Psychology
  • Religion
  • Social Sciences
  • Language
  • Pure Science
  • Applied Sciences
  • Art & Recreation
  • Literature
  • History & Geography
Icons made by Freepik from www.flaticon.com
Advanced Search