ANALISA JATUH TEGANGAN TRANSFORMATOR DISTRIBUSI PADA PENYULANG DI GARDU INDUK SUNGAI KEDUKAN RAYON AMPERA
Electricity is a basic need for society today. Equipment that is used every day requires electrical power to function properly. Distribution channel is an important channel so that electrical energy produced from power plants reaches consumers. In the distribution system there is a distribution transformer which plays an important role in the distribution process. This study aims to calculate the value of the drop voltage that occurs in the distribution transformer at the gurami feeder at the Sungai Kedukan Substation Rayon Ampera and analyze the effect of the length of the distribution line on the drop voltage that occurs in the distribution transformer. The research was conducted by collecting data at ULPL Ampera in the form of transformer load data, line length and type of conductor used and then processing the data that has been obtained to get the value of line current and drop voltage for each distribution substation. The largest voltage drop that occurs is 37.2926 V at the PD0038 substation with a line length of 2.6 km. The magnitude of the value of the drop voltage is due to the influence of the length of the line so that the improvement of the line distance is needed so that the transformer performance can be more optimal.